New Original Bently Nevada 3500/60-01-00 163179-01+133819-01 in Stock

The Bently Nevada 3500/60-01-00 is a 6-Channel Temperature Monitor for the 3500 Machinery Protection System. The complete configuration consists of the 163179-01 Temperature Monitor (main card) and the 133819-01 RTD/TC I/O Module with internal terminations.

  • Artikelnummer :

    63179-01+133819-01
  • Bestellung (Mindestbestellmenge) :

    1 Piece
  • Zahlung :

    EXW/CIF
  • Produktursprung :

    USA
  • Verschiffungshafen :

    Wuhan
  • Lieferzeit :

    3-5days
  • Gewicht :

    3kg
  • Product Details

     
     
    Specification Description
    Manufacturer Bently Nevada (Baker Hughes) 
    Model 3500/60-01-00
    Main Card Part Number 163179-01 
    I/O Module Part Number 133819-01 (RTD/TC Non-Isolated, Internal Terminations) 
    Product Type 6-Channel Temperature Monitor
    Number of Channels 6 independent channels 
    Supported Sensors RTD: 2-/3-/4-wire Pt100, Pt1000, Ni120, Cu10; TC: J, K, E, T, B, R, S, N 
    Input Impedance >10 MΩ per lead input 
    RTD Current Source 925 ±15 µA @ 25°C per transducer 
    Accuracy ±0.5°C typical (RTD); ±1°C to ±2°C typical (TC) 
    Update Rate 1 second per channel 
    Power Consumption 7 W typical (3500/60); 9 W (3500/61) 
    Recorder Output None (3500/61 provides recorder outputs) 
    Front Panel LEDs OK, TX/RX, Bypass 
    Operating Temperature -30°C to +65°C (-22°F to +150°F) 
    Storage Temperature -40°C to +85°C 
    Main Card Dimensions 241.3 mm x 24.4 mm x 163.1 mm 
    Main Card Weight Approx. 0.46 kg 
    I/O Module Weight Approx. 0.20 kg 
    Rack Space 1 full-height front slot + 1 full-height rear slot
    Safety Certification SIL 2 (IEC 61508) 
    Compliance API 670 
    Country of Origin USA 

    Related Product Model Recommendations

     
     
    Model Description Typical Application
    3500/60-01-00 (this model) Temperature Monitor with internal terminations (163179-01 + 133819-01) Standard temperature monitoring with internal wiring 
    3500/60-02-00 Temperature Monitor with external terminations (133827-01) Applications requiring external wiring access
    3500/60-03-00 Temperature Monitor with TC isolated I/O (133835-01) High-interference environments requiring 250 Vdc channel isolation 
    3500/61 Temperature Monitor with 4-20 mA recorder outputs per channel Applications requiring analog signal retransmission 
    3500/62 Process Variable Monitor Pressure, flow, level monitoring (4-20 mA / ±10V) 
    163179-01 Temperature Monitor Main Card Spare/replacement main card 
    133819-01 RTD/TC I/O Module with Internal Terminations Spare/replacement I/O module 

    FAQs

    Q1: What is the primary function of the 3500/60-01-00?

    It is a 6-channel Temperature Monitor that accepts RTD and thermocouple inputs, conditions the signals, and compares them against user-programmable alarm setpoints. When used in a Triple Modular Redundant (TMR) configuration, temperature monitors must be installed adjacent to each other in groups of three, employing two types of voting to ensure accurate operation and avoid single-point failures.

    Q2: What is the difference between the 3500/60 and the 3500/61?

    The 3500/60 and 3500/61 provide identical functionality except that the 3500/61 provides recorder outputs for each of its six channels, while the 3500/60 does not provide recorder outputs . The 3500/60 has a nominal power consumption of 7 W, while the 3500/61 consumes 9 W.

    Q3: What is the difference between 163179-01 and 133819-01?

    The 163179-01 is the Temperature Monitor main card (front panel) that processes the temperature signals and generates alarms. The 133819-01 is the RTD/TC I/O Module (rear module) that provides the physical terminal connections for field wiring. Both are required together to form a complete 3500/60-01-00 monitoring channel.

    Q4: Can the 3500/60-01-00 accept both RTD and TC inputs simultaneously?

    Yes. The RTD/TC non-isolated version (Option -01) can be configured to accept either TC or RTD inputs, or a mixture of TC and RTD inputs . The TC isolated version (Option -03) provides 250 Vdc of channel-to-channel isolation to protect against external interference.

    Q5: What are the typical applications for the 3500/60?

    It is widely used for monitoring radial bearing metal temperature, thrust bearing temperature, motor stator temperature, and inlet/outlet medium temperature on critical rotating machinery such as steam turbines, gas turbines, large compressors, and pump sets in power plants, petrochemical facilities, and other industrial applications.