Brief Introduction of Yokogawa
Yokogawa's main businesses: industrial automation and test and measurement hardware and software.
Yokogawa's products are used in a variety of industries that require process control systems. Depending on the size and requirements of the project, Yokogawa offers a variety of control systems: DCS, PLC, SCADA and ESD (Emergency Shutdown). Yokogawa has also partnered with Shell Global Solutions to provide advanced process control (APC) solutions for refineries, petrochemical plants, and chemical plants.
Detailed Information
AMM25C MV input multiplexer module with thermocouple interface (15 points, connector type, RJC input port added), 15 channels
|
Country of origin
|
Japan |
|
Product condition
|
New |
|
Warranty
|
one year |
|
Payment Method
|
T/T, Western Union
|
|
Shipping Method
|
DHL/FedEX/UPS/TNE/EMS
|
Company Introduction
SWAN ELECTRIC has been in the industrial control industry for many years, specializing in providing PLC, DCS, control system spare parts, drives, HIM, etc.
Main Brands: Rockwell-AB ¦ ABB ¦ Triconex ¦ Siemens ¦ ICS Triplex¦ Yaskawa ¦ Pilz ¦ Schneider ¦ Mitsubishi ¦ Honeywell ¦ GE Fanuc ¦ Sick ¦ Bently ¦Beckhoff¦ Omron ¦ Delta ¦ P+F ¦ Foxboro ¦Pilz ¦ B&R ¦Bachmann¦ Cisco¦MOXA¦B&R¦IFM......
The purpose of the SWAN ELECTRIC is to maintain the production cycle of the factory.

FAQ
Q1: What is the Yokogawa AMM25C used for?
It is a 15-channel mV input multiplexer module with a dedicated thermocouple interface and RJC input port for CENTUM CS/VP DCS systems, used to acquire low-level analog signals (DC voltage, mV, thermocouple, RTD) from field sensors .
Q2: How many channels does it have?
15 input channels. Channel 16 is dedicated to the RJC (Reference Junction Compensation) port .
Q3: What is the difference between AMM22C and AMM25C?
The AMM22C is a 16-channel mV input multiplexer without a dedicated RJC input port. The AMM25C provides 15 input channels plus a dedicated RJC input port for thermocouple reference junction compensation .
Q4: What is the input range?
For mV: -100 to +100 mV DC. For DC voltage: -10 to +10 V DC. For RTD: -200 to +600 °C .
Q5: What cable is required?
The AMM25C requires a KS1 cable for field wiring (connector type) .
Q6: Does it provide channel-to-channel isolation?
Yes, input signals are isolated between systems with a withstanding voltage of 1500 V AC/min .
Q7: What is the burnout detection behavior?
Selectable UP / DOWN / OFF. When a thermocouple breaks, the signal can be forced to a known state to trigger alarms .
Q8: Is this a current or legacy product?
The AMM25C is associated with CENTUM CS/VP systems and is primarily sourced as a spare part for existing installations. Confirm current availability with Yokogawa or an authorized distributor.
Q9: Where can I get technical documentation?
The official Yokogawa product print page (tek-international.com) is the most authoritative source in the search results for the AMM25C specification . For the exact order number, consult Yokogawa or an authorized distributor.