Honeywell 51401573-150 MC-TAMT12 Low-Level MUX Thermocouple FTA with Remote CJR, Conformally Coated

The Honeywell 51401573-150 is the MC-TAMT12 Low-Level Multiplexer (LLMUX) Thermocouple Field Termination Assembly (FTA) for the Honeywell TDC 3000 / Experion PKS distributed control system (DCS). It is the conformally coated, non-CE compliant variant, designed to provide field termination for 16 thermocouple input channels with a remote Cold Junction Reference (CJR) connection.

  • Artikelnummer :

    51401573-150
  • Bestellung (Mindestbestellmenge) :

    1
  • Zahlung :

    EXW
  • Produktursprung :

    USA
  • Verschiffungshafen :

    Wuhan, Hubei, China
  • Lieferzeit :

    3-5 days
  • Gewicht :

    0.5KG
  • Products Description

    Honeywell 51401573-150 MC-TAMT12 new and original in stock

    Model Number 51401573-150 MC-TAMT12
    Place of Origin USA
    Dimension/Weight 0.5 kg
    Condition new and original
    Warranty 1 year
    Shipping term
    DHL Fedex TNT EMS UPS
    Payment TT / Western Union
    Delivery Time 3-5 days
    Service
    24 Hours Online Service

    CC-TUIO31

    Our Advantage

    Competitive Price

    For our original products, every product has a good discount.

    Professional Sales Team

    We have a sales team with strong professional knowledge and rich experience.

    Fast Delivery

    We have large warehouse for goods.Keep lots of goods in warehouse. so we could promise fast delivery.

     

      

    Applications

    • Refining and petrochemicals — multi-point temperature monitoring of reactors, distillation columns, and furnaces.

    • Power generation — boiler and turbine temperature measurement.

    • Harsh environment installations — where conformal coating is required for humidity or corrosive gas resistance.

    • Remote CJR applications — where the cold junction reference must be located away from the FTA for temperature stability.

    • Legacy TDC 3000 / Experion PKS maintenance — replacement and spare parts for existing installations.


    FAQ

    Q1: What is the Honeywell 51401573-150 (MC-TAMT12) used for?
    It is a 16-channel LLMUX Thermocouple Field Termination Assembly for Honeywell TDC 3000 / Experion PKS DCS. It provides field wiring termination for thermocouple inputs with a remote Cold Junction Reference (CJR) connection .

    Q2: How many channels does it have?
    16 thermocouple input channels .

    Q3: What is the difference between MC-TAMT12 and MU-TAMT12?
    The MC-TAMT12 (51401573-150) is the conformally coated variant. The MU-TAMT12 is the non-coated variant. Both use remote CJR connections .

    Q4: Is this FTA CE-compliant?
    No. The 51401573-150 is non-CE compliant .

    Q5: What is the difference between MC-TAMT12 and MC-TAMT02?
    The MC-TAMT12 uses a remote CJR connection (external sensor up to 50 m away). The MC-TAMT02 uses a local CJR on the FTA assembly .

    Q6: What remote CJR sensor and cable are required?
    The remote CJR sensor is Honeywell P/N 51304589-100. The cable is MU-KRCJ00 shielded 3-conductor cable, with a maximum length of 50 meters (164 feet) .

    Q7: Is this a current or legacy product?
    The TDC 3000 / Experion PKS is a legacy/mature platform. The 51401573-150 is primarily available as spare or refurbished stock. Confirm availability with Honeywell or an authorized distributor.

    Q8: Where can I get technical documentation?
    Official Honeywell documentation, or an authorized distributor, is the authoritative source for specifications and compatibility.


    Recommending Models

     
     
    Model Description When to Choose
    51401573-150 (MC-TAMT12) LLMUX TC FTA, 16-channel, remote CJR, conformally coated, non-CE When conformal coating and remote CJR are required for thermocouple measurement in harsh environments
    MU-TAMT12 LLMUX TC FTA, 16-channel, remote CJR, non-coated When conformal coating is not necessary (standard environment)
    MU-TAMT02 / MC-TAMT02 LLMUX TC FTA, 16-channel, local CJR When a local cold junction reference on the FTA is acceptable
    MU-TAMR02 / MC-TAMR02 LLMUX RTD FTA, 16-channel When RTD (Pt100) temperature measurement is required instead of thermocouple
    MU-PLAM02 / MC-PLAM02 LLMUX IOP The required IOP for use with the MC-TAMT12 FTA
Eine Nachricht hinterlassen
Wenn Sie an unseren Produkten interessiert sind und mehr Details erfahren möchten, hinterlassen Sie bitte hier eine Nachricht. Wir werden Ihnen so schnell wie möglich antworten.
Eine Nachricht hinterlassen
Wenn Sie an unseren Produkten interessiert sind und mehr Details erfahren möchten, hinterlassen Sie bitte hier eine Nachricht. Wir werden Ihnen so schnell wie möglich antworten.